In automation technology, transmitters create an electric signal ranging from 0/4 mA…20 mA that is proportional to a measured signal (i.e. temperature, pressure, differential pressure, fill level, flow volume).
Whether you want to connect 2-wire and 3-wire transmitters or active signals coming from externally supplied field devices and 4-wire transmitters, as part of our remote I/O solution &ldqou;LB system”, we offer highly reliable analog modules with Ex i inputs for use in Zone 2 or Class I/Div. 2 explosion hazardous areas. These modules not only power the connected transmitter, but also digitize the measured current for bus communication. Several of these transmitter power supplies can also be used for connection of 3-wire transmitters up to 23 mA. In these applications, the third wire is used for active return line current ranging from 4 mA…20 mA or 0 mA…20 mA.
Features:
- 1-channel versions address the needs of users that appreciate granularity of their system and easy commissioning.
- 4-channel versions ensure highest utilization of the backplanes used for module connection and enable compact remote I/O solutions with large channel numbers.
- The modules support lead breakage detection, short circuit detection, and live-zero status.
- Galvanic isolation separates the inputs from bus and power.
- Hot-swappable, which allows quick and easy module replacement without time-consuming system shutdowns.
Specifications:
- Number of Channels: 4
- Number of Slots: 1
- Electromagnetic Compatibility: NE 21:2007
- Protection: IEC 60529:2000
- Environmental Test: EN 60068-2-14:2009
- Shock Resistance: EN 60068-2-27:2009
- Vibration Resistance: EN 60068-2-6:2008
Downloads:
Data Sheet
Catalog