Designed to house high voltage connections within a hazardous area, the 4TJB can terminate up to 45kV power or multi-use cables.
The 4TJB can accept up to three single-phase connections (one conductor per phase) in either a bottom entry or through box configuration. The rugged enclosure is based on Abtech’s field-proven SX stainless steel junction box. It is DTS-01 deluge tested and fault rated to 40kA for one second.
The -125 variants offer a unique solution for the termination of offshore umbilical cables or onshore distribution systems. In this design, the power conductor compartment houses the HV cables. A separate control compartment is used for terminating fiber optic or control cables.
A thermostat-controlled heater can also be fitted to maintain a consistent internal temperature and prevent condensation build-up. The enclosure can be further configured with a sun canopy or painted to client-specific requirements.
- Up to 36kV in Zone 1 Areas
- Maximum current 312A
- DTS-01 deluge tested enclosure
- Heavy duty machined hinges with lift off cover pad-lockable cover for easy installation
- Enclosure Type: High Voltage
- Ingress Protection: IP66 to EN60529, Type 4X, DTS?01
- Impact Resistance: >7Nm (tested above 10 Nm)
- Material: 2mm 316L Stainless Steel (EN 1.4404) enclosure with orbital finish, silicone gasket and captive 316 stainless steel fasteners, 3mm 316L (EN 1.4404) Stainless Steel gland plate
- Maximum Terminations: 1 conductor per phase in & 1 conductor per phase out
- No. of Glands Plates: 1 bottom side
- Crimp Lugs: 6mm² to 630mm²
- Earthing: Via studs on enclosure, door and gland plates
- Mounting: Via 3mm thick external mounting straps, slotted upper strap for ease of installation
- Area Classification: Zone 1 & 21, Gas and Dust
- Apparatus Coding: II 2 GD T4 Gb, Ex tb IIIC T135°C Db
- Certificate Number: Sira 09ATEX3313X