7500 series type Z & Ex pzc purge and pressurization control unit
General specifications
Equipment architecture max. enclosure size 450 ft3 (12.7 m3)
Operating mode fully automatic (FA)
Series 7500
Hazardous environment gas or dust
Supply
Rated voltage 20 … 30 V DC at 0.1 A
90 … 250 V AC , 50 … 60 Hz at 0.04 A without solenoid valve
Supply voltage can be line-to-line or line-to-neutral, single phase
OVC II
Power consumption max. 2.7 W / 7.3 VA without valve
Electrical specifications
Connection screw terminals — see manual for specifications on wire size and torque values
Output
Output I
Connection K1, terminals, 1 x NO
Output type enclosure power contacts
Contact loading 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A
Output II
Connection K2, terminals, 1 x NO
Output type alarm and control contacts
Contact loading 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A
Output III
Connection K3, terminals, L1 powered contact
Output type solenoid manifold, contact
Inrush current 5 A
Contact loading 0.5 A at 250 V AC , 0.5 A at 30 V DC, relays must be externally fused
Indicators/settings
LED indication K1: Green – Contact K1 is energized (enclosure contacts)
K2: Amber – Contact K2 is energized (alarm/control contacts)
P/SV: Blue – Safe pressure P1 (minimum enclosure pressure)
P/SV: Amber – Solenoid manifold is energized (purging/pressure compensation)
Pneumatic parameters
Protective gas supply compressed air or inert gas, 5 µm filter, free from oil
Pressure requirement supply pressure: 20 … 120 psig (1.4 … 8.2 bar)
Safe pressure 0.25 in wc (0.63 mbar) minimum for gas
0.65 in wc (1.63 mbar) minimum for dust
Enclosure pressure 0 … 10 in wc (0 … 24.8 mbar)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 , FCC CFR 47, part 15, subpart B: 2017, Class A ICES-003, Issue 6:2016, Class A ITE
RoHS
Directive 2011/65/EU (RoHS) EN 50581:2012
Conformity
Accuracy pressure sensing: ± 0.125 in wc (0.31 mbar)
timers: ± 5 %
Ambient conditions
Ambient temperature Ambient temperature ranges depend on the T class. See the certificates.
Storage temperature -40 … 80 °C (-40 … 176 °F)
Relative humidity 5 … 90 %, non-condensing
Altitude max. 2000 m
Vibration resistance 5 … 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance 30 g, 11 ms, all axes
Mechanical specifications
Connection type electrical: 2 x 1/2 inch NPTF (open from factory)
1 x M12 opening (plugged from factory)
pneumatic: high-pressure port – 1/8 in NPTF, low-pressure port – 1/8 in NPTF
Degree of protection Type 4X , IP66
Material lens: Makrolon® GP-V polycarbonate
screws: AISI 316 (1.4401), 304, or 18-8 stainless steel
housing: A380, A356, or 6061-T6 aluminum
mounting gasket: Bisco® HT-800 medium cellular silicone
mounting tabs: SAE 304 stainless steel
M12 plug: 6061-T6 aluminum
Mass 710 g (1 lb 10 oz)
Dimensions 150 x 100 x 50 mm (5.9 x 4 x 2 in)
Data for application in connection with hazardous areas
Certificate
Marking Ex-Hexagon II 3 G Ex ec nC [pzc] IIC T6…T4 Gc
Ex-Hexagon II 3 D Ex tc [pzc] IIIC T60 °C … T80 °C Dc
International approvals
UL approval
cULus Class I, Division 2, Groups A, B, C, D T4 (-40 °C ≤ Ta ≤ 70 °C)
Class I, Division 2, Groups A, B, C, D T5 (-40 °C ≤ Ta ≤ 65 °C)
Class I, Division 2, Groups A, B, C, D, T6 (-40 °C ≤ Ta ≤ 50 °C)
Class II, Division 2, Groups F, G T4 (-40 °C ≤ Ta ≤ 70 °C)
Class II, Division 2, Groups F, G T5 (-40 °C ≤ Ta ≤ 65 °C)
Class II, Division 2, Groups F, G T6 (-40 °C ≤ Ta ≤ 50 °C)
IECEx approval Ex ec nC [pzc] IIC T6…T4 Gc
Ex tc [pzc] IIIC T60 °C … T80 °C Dc