Enclosure Filtered Fans are used to create optimum climates in enclosures. The interior temperature of an enclosure is reduced by expelling heated internal air by channeling cooled and filtered outside air into the enclosure. The resulting air flow prevents the formation of localized heat pockets and protects the electronic components from overheating. The plastic used to construct the cabinet hood is weather resistant, impact and UV light resistant.
Download – Filtered Fans FF018 Brochure
Features:
- The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
- Functional design of the intake and exhaust fan hoods are very effective at preventing direct infiltration of falling water and dust. The filter mat does not rapidly become contaminated with dirt and does not need to be exchanged as frequently as other options.
- Air channeling makes the filter fan particularly quiet during operation.
- All filtered fans models are available with an integrated airflow monitor.
- The direction of air flow can easily be switched by reversing the axial fan.
- EMC versions and other voltages are available upon request.
14 – 69 CFM
- Very low noise
- Minimal mounting depth
- Functional design
- Time-saving installation
- UV resistant plastic
Technical Data
Axial fan, ball bearing | service life min. 50,000 h at 77 F and 65 %RH aluminum fan body, plastic rotor |
Connection | 2 wires w/ cage clamps, AWG 14, length 4″ |
Housing (filter fan and exhaust filter) | plastic, UL 94V-0, light grey |
Hood (filter fan and exhaust filter) | plastic, UL 94V-0, light grey; UV light resistant according to UL 746C (f1) |
Mounting frame | with double-sided industrial adhesive for mounting to the outside of enclosure; certain operating
circumstances may make the additional use of screws necessary; cut-out template included |
Filter media rating | G4 acc. to DIN EN 779, filtering degree 94% |
Filter material | synthetic fiber with progressive construction, temperature resistant to 212F, self-extinguishing
class F1; moisture resistant to 100 %RH, reusable – can be cleaned by washing or vacuuming |
Operating / Storage temperature | +14 to +158 F (-10 to +70C ) / -40 to +158F (-40 to +70C) |
Operating / Storage humidity | max. 90 %RH (non-condensing) |
Protection class / Protection type | I (grounded) / IP55 (according to VDE), UL Type 12 |
Approvals | UL File No. E234324 (all), GOST TR (all), VDE (AC 230 V only) |
Available Models
12-14 CFM
*Click on model numbers below to get a quick quote.
Model | Operating
Voltage |
Air Volume,
Free Blowing |
Air Volume with
Exhaust Filter |
Consumption
Current/Power |
Average
Noise Level |
Mounting
Depth |
Enclosure
Cut-out |
Weight |
01800.0-00 | AC 230 V, 50 Hz | 12 cfm | 9 cfm | 80 mA / 13 W | 31 dB (A) | 1.8″ | 3.8″ x 3.8″ | 1.3 lbs. |
01800.0-01 | AC 120 V, 60 Hz | 14 cfm | 11 cfm | 160 mA / 13 W | 31 dB (A) | 1.8″ | 3.8″ x 3.8″ | 1.3 lbs. |
32-37 CFM
*Click on model numbers below to get a quick quote.
Model | Operating
Voltage |
Air Volume,
Free Blowing |
Air Volume with
Exhaust Filter |
Consumption
Current/Power |
Average
Noise Level |
Mounting
Depth |
Enclosure
Cut-out |
Weight |
01801.0-00 | AC 230 V, 50 Hz | 32 cfm | 25 cfm | 100 mA / 15 W | 40 dB (A) | 2.3″ | 4.9″ x 4.9″ | 2.2 lbs. |
01801.0-01 | AC 120 V, 60 Hz | 37 cfm | 28 cfm | 180 mA / 15 W | 40 dB (A) | 2.3″ | 4.9″ x 4.9″ | 2.2 lbs. |
60-69 CFM
*Click on model numbers below to get a quick quote.
Model | Operating
Voltage |
Air Volume,
Free Blowing |
Air Volume with
Exhaust Filter |
Consumption
Current/Power |
Average
Noise Level |
Mounting
Depth |
Enclosure
Cut-out |
Weight |
01802.0-00 | AC 230 V, 50 Hz | 60 cfm | 40 cfm | 100 mA / 15 W | 39 dB (A) | 3.4″ | 6.9″ x 6.9″ | 2.9 lbs. |
01802.0-01 | AC 120 V, 60 Hz | 69 cfm | 46 cfm | 180 mA / 15 W | 39 dB (A) | 3.4″ | 6.9″ x 6.9″ | 2.9 lbs. |
Product Download